Motor Current Calculator

Calculate Full Load Current for Single-Phase & Three-Phase Motors

💡 Formulas: Single Phase: I = P / (V × PF × η) | Three Phase: I = P / (√3 × V × PF × η)
I = P / (V × PF × η) (Single) | I = P / (√3 × V × PF × η) (Three)

📖 Motor Current Calculator

This tool calculates the full load current (FLC) for single-phase and three-phase induction motors. Proper current calculation is essential for selecting the correct circuit breaker, cable size, and motor protection devices.

📐 Motor Current Formulas

Single Phase: I = P / (V × PF × η)
Three Phase: I = P / (√3 × V × PF × η)
Starting Current: I_start = 5 to 7 × I_FLC

📊 Typical Motor Parameters

Power (kW)3-Phase Current @415VPFEff%Starting (A)
0.751.50.75807.5
1.52.80.788214
2.24.00.808320
3.76.50.828533
5.59.50.838748
7.513.00.858865
1118.50.868993
1525.00.8790125
2236.00.8891180
3760.00.8992300
5588.00.9093440
75120.00.9093600

📌 Motor Starting Current

❓ Frequently Asked Questions

How to calculate motor full load current?
Three phase: I = P / (√3 × V × PF × η). Single phase: I = P / (V × PF × η).
What is motor starting current?
Starting current is 5-7 times FLC for DOL starting.
How to convert HP to kW?
1 HP = 0.746 kW. Multiply HP by 0.746.
What is typical power factor for motors?
Small: 0.75-0.80. Medium: 0.80-0.85. Large: 0.85-0.90.