💡 Formulas: Single Phase: I = P / (V × PF × η) | Three Phase: I = P / (√3 × V × PF × η)
I = P / (V × PF × η) (Single) | I = P / (√3 × V × PF × η) (Three)
Calculate Full Load Current for Single-Phase & Three-Phase Motors
This tool calculates the full load current (FLC) for single-phase and three-phase induction motors. Proper current calculation is essential for selecting the correct circuit breaker, cable size, and motor protection devices.
| Power (kW) | 3-Phase Current @415V | PF | Eff% | Starting (A) |
|---|---|---|---|---|
| 0.75 | 1.5 | 0.75 | 80 | 7.5 |
| 1.5 | 2.8 | 0.78 | 82 | 14 |
| 2.2 | 4.0 | 0.80 | 83 | 20 |
| 3.7 | 6.5 | 0.82 | 85 | 33 |
| 5.5 | 9.5 | 0.83 | 87 | 48 |
| 7.5 | 13.0 | 0.85 | 88 | 65 |
| 11 | 18.5 | 0.86 | 89 | 93 |
| 15 | 25.0 | 0.87 | 90 | 125 |
| 22 | 36.0 | 0.88 | 91 | 180 |
| 37 | 60.0 | 0.89 | 92 | 300 |
| 55 | 88.0 | 0.90 | 93 | 440 |
| 75 | 120.0 | 0.90 | 93 | 600 |