Transformer Rating Calculator

Calculate kVA Rating, Primary & Secondary Current, Voltage & Turns Ratio

šŸ’” Formulas: kVA = (V Ɨ I) / 1000 (Single) | kVA = (√3 Ɨ V Ɨ I) / 1000 (Three)
kVA = V Ɨ I / 1000 (Single) | kVA = √3 Ɨ V Ɨ I / 1000 (Three)

šŸ“– Transformer Rating Calculator

This tool helps you calculate the kVA rating of a transformer based on primary voltage, secondary voltage, and load current. It also computes primary and secondary currents, turns ratio, and provides standard transformer sizes. Essential for transformer sizing and electrical design.

šŸ“ Transformer Formulas

Single Phase: kVA = (V Ɨ I) / 1000
Three Phase: kVA = (√3 Ɨ V Ɨ I) / 1000
Turns Ratio: N₁/Nā‚‚ = V₁/Vā‚‚
Primary Current: I₁ = (Vā‚‚ Ɨ Iā‚‚) / V₁

šŸ“Š Standard Transformer kVA Ratings

kVAPrimary (11kV) CurrentSecondary (415V) Current
251.3A34.8A
502.6A69.6A
1005.2A139A
20010.5A278A
31516.5A438A
50026.2A696A
63033.1A877A
100052.5A1392A
160084.0A2228A
2000105.0A2785A

šŸ“Œ Transformer Sizing Guide

šŸ’” Transformer Types & Applications

ā“ Frequently Asked Questions

How to calculate transformer kVA rating? ā–¼
Single phase: kVA = V Ɨ I / 1000. Three phase: kVA = √3 Ɨ V Ɨ I / 1000.
What is the formula for transformer turns ratio? ā–¼
Turns ratio = N₁/Nā‚‚ = V₁/Vā‚‚. For 11kV/415V, ratio = 11000/415 = 26.5.
How to calculate primary current from secondary current? ā–¼
I₁ = (Vā‚‚ Ɨ Iā‚‚) / V₁. For 11kV/415V with 100A secondary, I₁ = 3.77A.
Single phase vs three phase transformer? ā–¼
Single phase has one winding set. Three phase has three sets and uses √3 factor. Three phase is more efficient for industrial loads.
What size transformer do I need for my load? ā–¼
Calculate total load in kVA, add 20-30% for future expansion, select next standard rating above this value.
What are standard transformer kVA ratings? ā–¼
Standard ratings: 25, 50, 63, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500 kVA.