Transformer Rating Calculator

Calculate kVA Rating, Primary & Secondary Current, Voltage & Turns Ratio

šŸ’” Formulas: kVA = (V Ɨ I) / 1000 (Single) | kVA = (√3 Ɨ V Ɨ I) / 1000 (Three)
kVA = V Ɨ I / 1000 (Single) | kVA = √3 Ɨ V Ɨ I / 1000 (Three)

šŸ“– Transformer Rating Calculator

This tool helps you calculate the kVA rating of a transformer based on primary voltage, secondary voltage, and load current. It also computes primary and secondary currents, turns ratio, and provides standard transformer sizes. Essential for transformer sizing and electrical design.

šŸ“ Transformer Formulas

Single Phase: kVA = (V Ɨ I) / 1000
Three Phase: kVA = (√3 Ɨ V Ɨ I) / 1000
Turns Ratio: N₁/Nā‚‚ = V₁/Vā‚‚
Primary Current: I₁ = (Vā‚‚ Ɨ Iā‚‚) / V₁

Where:
V₁ = Primary Voltage (V)   Vā‚‚ = Secondary Voltage (V)
I₁ = Primary Current (A)   Iā‚‚ = Secondary Current (A)

šŸ“Š Standard Transformer kVA Ratings

kVAPrimary (11kV) CurrentSecondary (415V) CurrentApplication
251.3A34.8ASmall commercial
502.6A69.6ASmall commercial
1005.2A139ASmall industrial
20010.5A278AIndustrial
31516.5A438AMedium industrial
50026.2A696ALarge industrial
63033.1A877ALarge industrial
100052.5A1392AHeavy industrial
160084.0A2228AHeavy industrial
2000105.0A2785APower distribution

šŸ“Œ Transformer Sizing Guide

šŸ’” Transformer Types & Applications

šŸ”§ How to Use This Calculator

ā“ Frequently Asked Questions (FAQ)

ā“ How to calculate transformer kVA rating? ā–¼
For single phase: kVA = V Ɨ I / 1000. For three phase: kVA = √3 Ɨ V Ɨ I / 1000. Enter voltage and current to get kVA rating.
ā“ What is the formula for transformer turns ratio? ā–¼
Turns ratio = N₁/Nā‚‚ = V₁/Vā‚‚. For example, 11kV/415V transformer has turns ratio = 11000/415 = 26.5.
ā“ How to calculate primary current from secondary current? ā–¼
I₁ = (Vā‚‚ Ɨ Iā‚‚) / V₁. For a 11kV/415V transformer with 100A secondary current, primary current = (415 Ɨ 100) / 11000 = 3.77A.
ā“ What is the difference between single phase and three phase transformer? ā–¼
Single phase has one primary and one secondary winding. Three phase has three sets of windings and uses √3 factor in calculations. Three phase is more efficient for industrial loads.
ā“ What size transformer do I need for my load? ā–¼
Calculate total load in kVA, add 20-30% for future expansion, and select the next standard kVA rating above this value. Use this calculator to verify sizing.
ā“ What is the standard transformer kVA rating? ā–¼
Standard ratings: 25, 50, 63, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500 kVA.